PROCESS INSTRUCTIONS FOR COVERAGE OF CEILINGS

30 minutes 1 x 12 mm or 2 x 9 mm

  • Ceiling employment below wood or steel beams with and without sound requirements
  • Material
  •  1 x 12 mm or 2 x 9 mm Permoxxboard.
  • handling 1 x 12 wood
  • sheet 12 mm, riveted C-C 100mm on wooden rafters. between the rafters wooden strips 45 x 45 C-C 600mm, blunt seams on the wooden laths. Put rock wool 35kg/m3 40mm between the beams.
  • Handling 2x9mm
  • 1st sheet 9mm screwed, C-C 300mm on wooden strips, 2nd sheet sight side riveted on 1st sheet (covering the seams of 1st sheet), distance between screws 150mm. Staples, length 22 mm. Put rock wool 35kg/m3 40mm between the beams
  • Seams
    for further finishing of the sight consult the processing advice on our website. WWW.Permoxx.com 
  • Seams 2 – 4 mm have always to be glued with fire-resistant glue or kit
  • Edges (with and without demands for sound)
  • Screwed hardwood edge laths apply with rock wool strip to the wall
  • Edges (with demands for sound)
  • Screwed hardwood edge laths apply with rock wool strip to the wall with steel rails on ANR ceiling hangers (for lower demands deviations possible).
  • Test reports
    For fully detailed construction always consult the construction in the certificate
  • Fire-resistance:
    Efectis Raport 2x9mm 2012-Efectis-R9196c 1x12mm 2013-Efectis-R1470a