PROCESS INSTRUCTIONS FOR COVERAGE OF CEILINGS

60 minutes 1 x 12 mm or 2 x 9 mm

Ceiling employment below wood or steel beams with and without sound requirements

  • Material
  • 1 x 12 mm or 2 x 9 mm Permoxxboard.
  • Handling 1 x 12 mm wood
  • Sheet 12mm, riveted C-C 100mm on wooden rafters. Between the rafters wooden strips 45 x 45 C-C 600mm, blunt seams on the wooden laths. Put rock wool 35kg/m3 40mm between the beams.
  • Handling
    2x9mm
  • 1st sheet 9mm screwed, C-C 300mm on wooden strips, 2nd sheet 9mm sheet sight side riveted on 1st sheet (covering the seams of 1st sheet), distance between screws 150mm. Staples, length 22 mm. Put rock wool 35kg/m3 40mm between the beams
  • Seams
  • For further finishing of the sight consult the processing advice on our website. www.permoxx.com
  • Seams 2 – 4 mm have always to be glued with fire-resistant glue or kit
  • Fire-resistance:
    Efectis Rapport: 2x9mm 2012-Efectis-R9196c 1x12mm 2013-Efectis-R1470a