img

PRCESS INSTRUCTIONS FOR COVERAGE OF PILLARS

120 minutes 12 + 18 mm or 2 x 18 mm

Pillar processing 3- or 4-fold covered

  • Material
  • 12 + 18 mm or 2 x 18 mm Permoxboard. (Look on basic of profile number in the processing book from page 48)
  • Handling
  • 12 + 18 mm or 2 x 18 mm Permoxxboard. Interconnection between sheets riveted with 32 mm staples C-C 100 mm. (second sheet must cover the seams or first sheet) 18 mm Permoxxboard strips 100 mm broad behind seams between vertical sheets riveted with 32 mm staples C-C 100 mm. (see diagrammes).
  • Seams
  • for further finishing of the sight consult the processing advice on our website. www.permoxx.com
  • Seams
  • 2 – 4 mm have always to be glued with fire-resistant glue or kit
  • Edges (with and without demands for noise)
  • Not applicable
  • Test reports
  • For fully detailed construction always consult the construction in the certificate
  • Fire-resistance:
    Efectis Raport:
  • 2012-Efectis exploratory examination (contact Permoxx for advice)
  • img