img

PROCESS INSTRUCTIONS FOR COVERAGE OF WALLS

30 minutes 1 x 12 mm

Partition wall up against pine rail or steel C profile (both sides)

  • Material
  • On both sides 1 x 9 mm Permoxxboard with wooden construction and 1 x 12 mm Permoxxboard with light weight steel construction
  • Handling 1 x 9 mm wooden construction
  • Both sides riveted, stainless steel staples 32mm C-C 100 mm, lath thickness 70 mm x 45 mm netto planed pine, C-C 600 mm. Fill the wall with rock wool 70 mm (35kg/m3). At the horizontal seams apply a covering strip of Permoxxboard.
  • Handling 1 x 12 mm
    Steel construction
  • Both sides screwed, C-C 100 mm, 70 mm rock wool (35 kg/m3) with matching C-75 and U75 profile 0,60 mm C-C 600 mm.
  • Seams
  • Lightweight steel construction: Seams 2 – 4 mm must always be glued with fire-resistant sealant. Wooden construction: Seams 2 – 4 mm must always be glued with fire-resistant sealant.
  • Edges
  • When applicable fill up the edges with strip of rock wool.
  • Fire-resistance:
    Efectis Raport:
  • 1x9mm 2013-Efectis-R0210D 1x12mm 2012-Efectis-R0490
  • img
  • Test reports
    For fully detailed construction always consult the construction in the certificate
  • Noise deadning:
    Ingenieurs Red: 20120122-01
  • Cauberg-Huygen

 

 

PROCESS INSTRUCTIONS FOR COVERAGE OF SHAFT WALLS AND SECONDARY WALLS

30 minutes 2 x 9 mm

Partition wall up against pine rail or steel C profile (both sides)

  • Material
  • On both sides 2 x 9 mm Permoxxboard
  • Handling
  • Metal C and U profile, breadth 75 mm and thickness 0,60 mm. On one side a 2 x Permoxxboard (9 mm) riveted (2nd sheet must cover seams of 1st sheet). 75 mm rock wool(35 kg/m3). With C-C 150 mm. Staples, length 22mm.
  • Seams
  • Seams 2 – 4 mm must always be glued with fire-resistant sealant.
  • Edges
  • When applicable fill up the edges with strips of rock wool.
  • Test reports
  • For fully detailed construction always consult the construction in the certificate
  • Fire-resistance:
    Efectis Raport:
  • 2012-Efectis-R9196a
  • img
  • Test reports
    For fully detailed construction always consult the construction in the certificate
  • Noise deadning:
    Ingenieurs Red: 20120122-01
  • Cauberg-Huygen

 

 

 

PROCESS INSTRUCTIONS FOR COVERAGE OF SECONDARY AND SHAFT WALLS TO PROTECT STEEL BUILDING MATERIALS

30 minutes 2 x 9 mm

Partition wall up against pine rail or steel C profile (both sides)

  • Material
  • On both sides 2 x 9 mm Permoxxboard
  • Handling
  • Metal C and U profile, breadth 75 mm and thickness 0,60 mm. On one side a 2 x Permoxxboard (9 mm) riveted (2nd sheet must cover seams of 1st sheet). 75 mm rock wool(35 kg/m3). With C-C 150 mm. Staples, length 22mm.
  • Seams
  • Seams 2 – 4 mm must always be glued with fire-resistant sealant.
  • Edges
  • When applicable fill up the edges with strip of rock wool.
  • Fire-resistance:
    Efectis Raport:
  • 2012-Efectis-R9196a
  • img
  • Test reports
    For fully detailed construction always consult the construction in the certificate
  • Noise deadning:
    Ingenieurs Red: 20120122-01
  • Cauberg-Huygen